8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the eldbus.
[0] Digital
input
Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial
communication port or eldbus option.
[2] Logic
AND
Activates the set-up selection via the eldbus/
serial communication port, and via 1 of the
digital inputs.
[3] * Logic OR Activates the set-up selection via the eldbus/
serial communication port, or via 1 of the
digital inputs.
8-56 Preset Reference Select
Option: Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
eldbus.
[0] Digital
input
Activates preset reference selection via a digital
input.
[1] Bus Activates preset reference selection via the
serial communication port or eldbus option.
[2] Logic AND Activates preset reference selection via the
eldbus/serial communication port, and via 1 of
the digital inputs.
[3] * Logic OR Activates the preset reference selection via the
eldbus/serial communication port, or via 1 of
the digital inputs.
8-90 Bus Jog 1 Speed
Range: Function:
100 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
xed jog speed via the serial port
or eldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
200 RPM* [ 0 - par. 4-13
RPM]
Enter the jog speed. Activate this
xed jog speed via the serial port
or eldbus option.
10-00 CAN Protocol
Option: Function:
NOTICE
The options depend on installed option.
[0] CANopen
[1] DeviceNet View the active CAN protocol.
10-01 Baud Rate Select
Select the eldbus transmission speed. The selection must
correspond to the transmission speed of the master and the
other eldbus nodes.
Option: Function:
[16] 10 Kbps
[17] 20 Kbps
[18] 50 Kbps
[19] 100 Kbps
[20] 125 Kbps
[21] 250 Kbps
[22] 500 Kbps
10-02 MAC ID
Range: Function:
Size related* [ 0 - 127] Selection of station address. Every
station connected to the same network
must have an unambiguous address.
10-05 Readout Transmit Error Counter
Range: Function:
0* [0 - 255 ] View the number of CAN control transmission
errors since the last power-up.
10-06 Readout Receive Error Counter
Range: Function:
0* [0 - 255 ] View the number of CAN control receipt errors
since the last power-up.
10-33 Store Always
Option: Function:
[0] * O Deactivates non-volatile storage of data.
[1] On
Stores parameter data received via VLT
®
DeviceNet
MCA 104 in EEPROM non-volatile memory as default.
10-50 Process Data Cong. Write
Only elements [2] and [3] of this array can be selected ([0] and
[1] are xed).
Option: Function:
[0] * None
[1] 16-80 Fieldbus CTW 1
[2] 16-82 Fieldbus REF 1
[3] 3-02 Minimum Reference
[4] 3-03 Maximum Reference
[5] 3-12 Catch Up/Slow Down Value
[6] 3-41 Ramp 1 Ramp Up Time
[7] 3-42 Ramp 1 Ramp Down Time
[8] 3-51 Ramp 2 Ramp Up Time
[9] 3-52 Ramp 2 Ramp Down Time
[10] 3-80 Jog Ramp Time
[11] 3-81 Quick Stop RampTime
[12] 4-11 Motor Speed Low Limit (RPM)
[13] 4-13 Motor Speed High Limit (RPM)
Parameters Programming Guide
MG92G102 Danfoss A/S © 06/2015 All rights reserved. 33