EasyManuals Logo

Danfoss VLT CDS 803 Programming Guide

Danfoss VLT CDS 803
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #51 background imageLoading...
Page #51 background image
13-20 SL Controller Timer
Range: Function:
74] Start timer X) and until the
timer value has elapsed. Array
parameters contain timers 0–7.
3.9.5 13-4* Logic Rules
Combine up to 3 boolean inputs (true/false inputs) from
timers, comparators, digital inputs, status bits, and events
using the logical operators AND, OR, and NOT. Select
boolean inputs for the calculation in parameter 13-40 Logic
Rule Boolean 1, parameter 13-42 Logic Rule Boolean 2, and
parameter 13-44 Logic Rule Boolean 3. Dene the operators
used to combine the selected inputs logically in
parameter 13-41 Logic Rule Operator 1 and
parameter 13-43 Logic Rule Operator 2.
. . .
. . .
. . .
. . .
Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
130BB673.10
Illustration 3.13 Logic Rules
Priority of calculation
The results of parameter 13-40 Logic Rule Boolean 1,
parameter 13-41 Logic Rule Operator 1, and
parameter 13-42 Logic Rule Boolean 2 are calculated rst.
The outcome (true/false) of this calculation is combined
with the settings of parameter 13-43 Logic Rule Operator 2
and parameter 13-44 Logic Rule Boolean 3, yielding the nal
result (true/false) of the logic rule.
13-40 Logic Rule Boolean 1
Array [6]
Select the rst boolean (TRUE or FALSE) input for the selected
logic rule.
Option: Function:
[0] * False Enters the xed value of FALSE in
the logic rule.
[1] True Enters the xed value TRUE in the
logic rule.
[2] Running See parameter 13-01 Start Event for
further description.
[3] In range See parameter 13-01 Start Event for
further description.
[4] On reference See parameter 13-01 Start Event for
further description.
13-40 Logic Rule Boolean 1
Array [6]
Select the rst boolean (TRUE or FALSE) input for the selected
logic rule.
Option: Function:
[7] Out of current
range
See parameter 13-01 Start Event for
further description.
[8] Below I low See parameter 13-01 Start Event for
further description.
[9] Above I high See parameter 13-01 Start Event for
further description.
[16] Thermal
warning
See parameter 13-01 Start Event for
further description.
[17] Mains out of
range
See parameter 13-01 Start Event for
further description.
[18] Reversing See parameter 13-01 Start Event for
further description.
[19] Warning See parameter 13-01 Start Event for
further description.
[20] Alarm (trip) See parameter 13-01 Start Event for
further description.
[21] Alarm (trip
lock)
See parameter 13-01 Start Event for
further description.
[22] Comparator 0 Use the result of comparator 0 in
the logic rule.
[23] Comparator 1 Use the result of comparator 1 in
the logic rule.
[24] Comparator 2 Use the result of comparator 2 in
the logic rule.
[25] Comparator 3 Use the result of comparator 3 in
the logic rule.
[26] Logic rule 0 Use the result of logic rule 0 in the
logic rule.
[27] Logic rule 1 Use the result of logic rule 1 in the
logic rule.
[28] Logic rule 2 Use the result of logic rule 2 in the
logic rule.
[29] Logic rule 3 Use the result of logic rule 3 in the
logic rule.
[30] SL Time-out 0 Use the result of timer 0 in the
logic rule.
[31] SL Time-out 1 Use the result of timer 1 in the
logic rule.
[32] SL Time-out 2 Use the result of timer 2 in the
logic rule.
[33] Digital input
DI18
Use the value of DI18 in the logic
rule (High=TRUE).
Parameters Programming Guide
MG18P202 Danfoss A/S © 06/2019 All rights reserved. 49
3 3

Other manuals for Danfoss VLT CDS 803

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS 803 and is the answer not in the manual?

Danfoss VLT CDS 803 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS 803
CategoryDC Drives
LanguageEnglish

Related product manuals