Recommended max. fuse
Power Bussmann Ferraz- Shawmut Ferraz- Shawmut Littel fuse
[kW] JFHR2 J
JFHR2
1)
JFHR2
11 FWH-40 HSJ-40 - -
15 FWH-50 HSJ-50 - -
18 FWH-60 HSJ-60 - -
22 FWH-80 HSJ-80 - -
30 FWH-100 HSJ-100 - -
37 FWH-125 HSJ-125 - -
45 FWH-150 HSJ-150 - -
55 FWH-200 HSJ-200 A50-P-225 L50-S-225
75 FWH-250 HSJ-250 A50-P-250 L50-S-250
Table 3.14 380-500 V, Frame Sizes B and C
1)
Ferraz-Shawmut A50QS fuses may substitute for
A50P fuses.
Recommended max. fuse
Power Bussmann Bussmann Bussmann Bussmann Bussmann Bussmann
[kW] Type RK1 Type J Type T Type CC Type CC Type CC
11 KTS-R-35 JKS-35 JJS-35 - - -
15 KTS-R-45 JKS-45 JJS-45 - - -
18 KTS-R-50 JKS-50 JJS-50 - - -
22 KTS-R-60 JKS-60 JJS-60 - - -
30 KTS-R-80 JKS-80 JJS-80 - - -
37 KTS-R-100 JKS-100 JJS-100 - - -
45 KTS-R-125 JKS-125 JJS-125 - - -
55 KTS-R-150 JKS-150 JJS-150 - - -
75 KTS-R-175 JKS-175 JJS-175 - - -
Table 3.15 525-600 V, Frame Sizes B and C
Recommended max. fuse
Power SIBA Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
[kW] Type RK1 Type RK1 Type RK1 J
11 5014006-040 KLS-R-035 A6K-35-R HSJ-35
15 5014006-050 KLS-R-045 A6K-45-R HSJ-45
18 5014006-050 KLS-R-050 A6K-50-R HSJ-50
22 5014006-063 KLS-R-060 A6K-60-R HSJ-60
30 5014006-080 KLS-R-075 A6K-80-R HSJ-80
37 5014006-100 KLS-R-100 A6K-100-R HSJ-100
45 2028220-125 KLS-R-125 A6K-125-R HSJ-125
55 2028220-150 KLS-R-150 A6K-150-R HSJ-150
75 2028220-200 KLS-R-175 A6K-175-R HSJ-175
Table 3.16 525-600 V, Frame Sizes B and C
1)
170M fuses shown from Bussmann use the -/80
visual indicator. –TN/80 Type T, -/110 or TN/110
Type T indicator fuses of the same size and
amperage may be substituted.
How to Install
Operating Instructions VLT
®
CDS302 and CDS303
MG34M302 - VLT
®
is a registered Danfoss trademark/Commercial Compressor 33