6.2 Parameters: 0-** Operation and Display
6.2.1 0-0* Basic Settings
0-01 Language
Option: Function:
Defines the language to be used in display.
[0] * English
[1] German
[2] French
[3] Danish
[4] Spanish
[5] Italian
0-02 Motor Speed Unit
Option: Function:
Select display of motor speed parameters (i.e.
references, feedbacks and limits) in terms of shaft
speed (RPM) or output frequency to the motor (Hz).
[0] * RPM
[1] Hz
NOTE
This parameter cannot be adjusted while the motor is
running.
0-04 Operating State at Power-up (Hand)
Option: Function:
Selects the operating mode upon
reconnection of the frequency converter to
mains voltage after power down in Hand
(local) operation mode.
[0] Resume Restarts the frequency converter, maintaining
the same and the same start/stop settings
(applied by [Hand On/Off]) as before the
frequency converter was powered down.
[1] * Forced stop,
ref=old
Restarts the frequency converter with a
saved local reference, after mains voltage
reappears and after pressing [Hand On].
[2] Forced stop,
ref=0
Resets the local reference to 0 upon
restarting the frequency converter.
0-10 Active Set-up
Option: Function:
Select the set-up to control the frequency
converter functions.
[0] Factory setup Cannot be changed. It contains the Danfoss
data set, and can be used as a data source
when returning the other set-ups to a
known state.
[1] * Set-up 1
[1] Set-up 1 to [4] Set-up 4 are the four
separate parameter set-ups within which all
parameters can be programmed.
0-10 Active Set-up
Option: Function:
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Multi Set-up Remote selection of set-ups using digital
inputs and the serial communication port.
This set-up uses the settings from 0-12 This
Set-up Linked to. Stop the frequency
converter before making changes to open-
and closed loop functions
Use 0-51 Set-up Copy to copy a set-up to one or all other
set-ups. Stop the frequency converter before switching
between set-ups where parameters marked ‘not
changeable during operation’ have different values. To
avoid conflicting settings of the same parameter within
two different set-ups, link the set-ups together using
0-12 This Set-up Linked to. Parameters which are ‘not
changeable during operation’ are marked FALSE in the
parameter lists in 6.16 Parameter Lists.
0-11 Edit Set-up
Option: Function:
Select the set-up to be edited (i.e.
programmed) during operation; either the
active set-up or one of the inactive set-ups.
[0] Factory setup Cannot be edited but it is useful as a data
source to return the other set-ups to a
known state.
[1] * Set-up 1
[1] Set-up 1 to [4] Set-up 4 can be edited
freely during operation, independently of
the active set-up.
[2] Set-up 2
[3] Set-up 3
[4] Set-up 4
[9] Active Set-up Can also be edited during operation. Edit
the chosen set-up from a range of sources:
LCP, FC RS-485, FC USB or up to five fieldbus
sites.
Parameter Descriptions
Operating Instructions VLT
®
CDS302 and CDS303
46 MG34M302 - VLT
®
is a registered Danfoss trademark/Commercial Compressor
6
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT CDS302 and is the answer not in the manual?

Danfoss VLT CDS302 Specifications

General IconGeneral
BrandDanfoss
ModelVLT CDS302
CategoryDC Drives
LanguageEnglish

Related product manuals