13-01 Start Event
Option: Function:
[5] Torque limit
The torque limit, set in 4-16 Torque
Limit Motor Mode or 4-17 Torque Limit
Generator Mode, has been exceeded.
[6] Current limit The motor current limit, set in
4-18 Current Limit, has been
exceeded.
[7] Out of current
range
The motor current is outside the
range set in 4-18 Current Limit.
[8] Below I low The motor current is lower than set
in 4-50 Warning Current Low.
[9] Above I high The motor current is higher than set
in 4-51 Warning Current High.
[10] Out of speed range The speed is outside the range set in
4-52 Warning Speed Low and
4-53 Warning Speed High.
[11] Below speed low The output speed is lower than the
setting in 4-52 Warning Speed Low.
[12] Above speed high The output speed is higher than the
setting in 4-53 Warning Speed High.
[13] Out of feedb. range The feedback is outside the range set
in 4-56 Warning Feedback Low and
4-57 Warning Feedback High.
[14] Below feedb. low The feedback is below the limit set in
4-56 Warning Feedback Low.
[15] Above feedb. high The feedback is above the limit set in
4-57 Warning Feedback High.
[16] Thermal warning The thermal warning turns on when
the temperature exceeds the limit in
the motor, the frequency converter,
the brake resistor or the thermistor.
[17] Mains out of range The mains voltage is outside the
specified voltage range.
[18] Reversing The output is high when the
frequency converter is running
counter clockwise (the logical
product of the status bits “running”
AND “reverse”).
[19] Warning A warning is active.
[20] Alarm (trip) A (trip) alarm is active.
[21] Alarm (trip lock) A (Trip lock) alarm is active.
[22] Comparator 0 Use the result of comparator 0.
[23] Comparator 1 Use the result of comparator 1.
[24] Comparator 2 Use the result of comparator 2.
[25] Comparator 3 Use the result of comparator 3.
[26] Logic rule 0 Use the result of logic rule 0.
[27] Logic rule 1 Use the result of logic rule 1.
13-01 Start Event
Option: Function:
[28] Logic rule 2 Use the result of logic rule 2.
[29] Logic rule 3 Use the result of logic rule 3.
[33] Digital input DI18 Use the result of digital input 18.
[34] Digital input DI19 Use the result of digital input 19.
[35] Digital input DI27 Use the result of digital input 27.
[36] Digital input DI29 Use the result of digital input 29.
[37] Digital input DI32 Use the result of digital input 32.
[38] Digital input DI33 Use the result of digital input 33.
[39] Start command A start command is issued.
[40] Drive stopped A stop command (Jog, Stop, Qstop,
Coast) is issued – and not from the
SLC itself.
[41] Reset Trip A reset is issued
[42] Auto-reset Trip An Auto reset is performed.
[43] Ok key The [OK] key is pressed.
[44] Reset key The [Reset] key is pressed.
[45] Left key
The [◄] key is pressed.
[46] Right key
The [►] key is pressed.
[47] Up key
The [
▲
] key is pressed.
[48] Down key
The [
▼
] key is pressed.
[50] Comparator 4 Use the result of comparator 4.
[51] Comparator 5 Use the result of comparator 5.
[60] Logic rule 4 Use the result of logic rule 4.
[61] Logic rule 5 Use the result of logic rule 5.
[94] RS Flipflop 0
[95] RS Flipflop 1
[96] RS Flipflop 2
[97] RS Flipflop 3
[98] RS Flipflop 4
[99] RS Flipflop 5
[100] RS Flipflop 6
[101] RS Flipflop 7
13-02 Stop Event
Select the boolean (TRUE or FALSE) input to activate Smart Logic
Control.
Option: Function:
[0] * False
For descriptions [0]-[61], see
13-01 Start Event Start Event
[1] True
[2] Running
[3] In range
[4] On reference
[5] Torque limit
[6] Current limit
Parameter Descriptions
Operating Instructions VLT
®
CDS302 and CDS303
MG34M302 - VLT
®
is a registered Danfoss trademark/Commercial Compressor 83