13-03 Reset SLC
Option: Function:
[0] * Do not reset
SLC
Retains programmed settings in all
parameter group 13-** Smart Logic Control.
[1] Reset SLC Resets all parameters in parameter group
13-** Smart Logic Control to default
settings.
6.10.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
fixed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
Illustration 6.14
In addition, there are digital values that will be compared
to fixed time values. See explanation in 13-10 Comparator
Operand. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to programme
Comparator 0, select index 1 to programme Comparator 1,
and so on.
13-10 Comparator Operand
Array [6]
Option: Function:
Choices [1] to [31] are variables which
will be compared based on their
values. Choices [50] to [186] are digital
values (TRUE/FALSE) where the
comparison is based on the amount of
time during which they are set to
TRUE or FALSE, respectively. See
13-11 Comparator Operator.
Select the variable to be monitored by
the comparator.
[0] * DISABLED The comparator is disabled.
[1] Reference The resulting remote reference (not
local) as a percentage.
[2] Feedback In the unit [RPM] or [Hz]
[3] Motor speed [RPM] or [Hz]
[4] Motor current [A]
13-10 Comparator Operand
Array [6]
Option: Function:
[5] Motor torque [Nm]
[6] Motor power [kW] or [hp]
[7] Motor voltage [V]
[8] DC-link voltage [V]
[9] Motor thermal Expressed as a percentage.
[10] Drive thermal Expressed as a percentage.
[11] Heat sink temp. Expressed as a percentage.
[12] Analog input AI53 Expressed as a percentage.
[13] Analog input AI54 Expressed as a percentage.
[14] Analog input
AIFB10
[V]. AIFB10 is internal 10 V supply.
[15] Analog input
AIS24V
[V] Analog input AICCT [17] [°]. AIS24V
is switch mode power supply: SMPS
24V.
[17] Analog input
AICCT
[°]. AICCT is control card temperature.
[18] Pulse input FI29 Expressed as a percentage.
[19] Pulse input FI33 Expressed as a percentage.
[20] Alarm number The error number.
[21] Warning number
[22] Analog input x30
11
[23] Analog input x30
12
[30] Counter A Number of counts
[31] Counter B Number of counts
[50] FALSE Enters the fixed value of false in the
comparator.
[51] TRUE Enters the fixed value of true in the
comparator.
[52] Control ready The control board receives supply
voltage
[53] Drive ready The frequency converter is ready for
operation and applies a supply signal
on the control board.
[54] Running The motor is running.
[55] Reversing The output is high when the
frequency converter is running counter
clockwise (the logical product of the
status bits “running” AND “reverse”)
[56] In range The motor is running within the
programmed current and speed
ranges set in 4-50 Warning Current Low
to 4-53 Warning Speed High.
[60] On reference The motor is running on reference.
Parameter Descriptions
Operating Instructions VLT
®
CDS302 and CDS303
MG34M302 - VLT
®
is a registered Danfoss trademark/Commercial Compressor 85