13-10 Comparator Operand
Array [6]
Option: Function:
Linked to hand Auto, at the same time
as the LCP is in Hand On mode.
[181] Remote ref. active
High when 3-13 Reference Site= [1]
Remote or [0] Linked to hand/auto,
while the LCP is in Auto On mode.
[182] Start command High when there is an active start
command, and no stop command.
[183] Drive stopped A stop command (Jog, Stop, Qstop,
Coast) is issued and not from the
SLC itself.
[185] Drive in hand
mode
High when the frequency converter is
in hand mode.
[186] Drive in auto
mode
High when the frequency converter is
in auto mode.
[187] Start command
given
[190] Digital input x30 2
[191] Digital input x30 3
[192] Digital input x30 4
[193] Digital input x46 1
[194] Digital input x46 2
[195] Digital input x46 3
[196] Digital input x46 4
[197] Digital input x46 5
[198] Digital input x46 6
[199] Digital input x46 7
13-11 Comparator Operator
Array [6]
Option: Function:
Select the operator to be used in the
comparison. This is an array parameter
containing comparator operators 0 to 5.
[0] < The result of the evaluation is TRUE, when
the variable selected in 13-10 Comparator
Operand is smaller than the fixed value in
13-12 Comparator Value. The result is FALSE,
if the variable selected in 13-10 Comparator
Operand is greater than the fixed value in
13-12 Comparator Value.
[1] * (equal) The result of the evaluation is TRUE, when
the variable selected in 13-10 Comparator
Operand is approximately equal to the fixed
value in 13-12 Comparator Value.
[2] > Inverse logic of option < [0].
[5] TRUE longer
than..
[6] FALSE
longer than..
13-11 Comparator Operator
Array [6]
Option: Function:
[7] TRUE shorter
than..
[8] FALSE
shorter
than..
13-12 Comparator Value
Array [6]
Range: Function:
Size related* [-100000.000 -
100000.000 ]
Enter the ‘trigger level’ for the
variable that is monitored by
this comtor. This is an array
parameter containing comtor
values 0 to 5.
6.10.4 13-1* RS Flip Flops
The Reset-Set Flip Flops hold the signal until set/reset.
Par. 13-15
RS-FF Operand S
Par. 13-16
RS-FF Operand R
130BB959.10
Illustration 6.15
Two parameters are used and the output can be used in
the logic rules and as events.
R
S
Flip Flop Output
130BB960.10
Illustration 6.16
The two operators can be selected from a long list. As a
special case, the same digital input can be used as both
Set and Reset, making it possible to use the same digital
input as start/stop. The following settings can be used to
set up the same digital input as start/stop (example given
with DI32 but is not a requirement).
Parameter Setting Notes
13-00 SL Controller Mode On
13-01 Start Event TRUE
13-02 Stop Event FALSE
Parameter Descriptions
Operating Instructions VLT
®
CDS302 and CDS303
MG34M302 - VLT
®
is a registered Danfoss trademark/Commercial Compressor 87