7.2.3.2 Status Word (Read-only)
Use the structure in Table 7.6 to query the status of the soft starter.
Bit Function Details MCD 201 MCD 202 MCD 500
0 Ready 0 = Start or stop command not acceptable
1 = Start or stop command acceptable
1 Control from net 0 = Program mode
1 = Control from net
2 Coasting 0 = Coasting
1 = Enabled
3 Trip 0 = Not tripped
1 = Tripped
4 Reserved Must be 0
5 Reserved Must be 0
6 Reserved Must be 0
7 Warning 0 = No warning
1 = Warning
8 Ramping 0 = Not at full voltage (non-bypassed)
1 = Running (full voltage at the motor)
9 Local/remote 0 = Local control
1 = Remote control
10 Reserved Must be 0
11 On 0 = Unknown, not ready, ready to start, or tripped
1 = Starting, running, stopping, or jogging
12 Reserved Must be 0
13 Reserved Must be 0
14 Reserved Must be 0
15 Temperature limit 0 = Motor operating below normal operating temperature
1 = Motor operating above normal operating temperature
Table 7.6 Status Commands
Packet Structures Installation Guide
MG17Q102 Danfoss A/S © 05/2017 All rights reserved. 15