8-90 Bus Jog 1 Speed
Range: Function:
100
RPM
*
[0 - par. 4-13 RPM] Enter the jog speed. This is a fixed jog speed activated via the
serial port or fieldbus option.
8-91 Bus Jog 2 Speed
Range: Function:
200
RPM
*
[0 - par. 4-13 RPM] Enter the jog speed. This is a fixed jog speed activated via the
serial port or fieldbus option.
10-00 CAN Protocol
Option: Function:
[0] CANopen
[1]
*
DeviceNet View the active CAN protocol.
NB!
The options depend on installed option.
10-01 Baud Rate Select
Option: Function:
[16] 10 Kbps
[17] 20 Kbps
[18]
[19]
50 Kbps
100 Kbps
[20]
*
125 Kbps
[21] 250 Kbps
[22] 500 Kbps Select the fieldbus transmission speed. The selection must cor-
respond to the transmission speed of the master and the other
fieldbus nodes.
10-02 MAC ID
Range: Function:
63
*
[0 - 127 ] Selection of station address. Every station connected to the
same DeviceNet network must have an unambiguous address.
10-05 Readout Transmit Error Counter
Range: Function:
0
*
[0 - 255] View the number of CAN control transmission errors since the
last power-up.
6. Parameters FC 100/ 200/ 300 DeviceNet
58
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
6

Other manuals for Danfoss VLT FC 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FC 100 Series and is the answer not in the manual?

Danfoss VLT FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT FC 100 Series
CategoryDC Drives
LanguageEnglish

Related product manuals