10-06 Readout Receive Error Counter
Option: Function:
[0] 0 - 255 View the number of CAN control receipt errors since the last
power-up.
10-07 Readout Bus Off Counter
Range: Function:
0
*
[0 - 255] View the number of Bus Off events since the last power-up.
10-10 Process Data Type Selection
Option: Function:
Select the Instance (telegram) for data transmission. The In-
stances available are dependent upon the setting of par. 8-10
Control Word Profile
.
When par. 8-10 is set to [0]
FC profile
, par. 10-10 options [0]
and [1] are available.
When par. 8-10 is set to [5]
ODVA
, par. 10-10 options [2] and
[3] are available.
Instances 100/150 and 101/151 are Danfoss-specific. Instances
20/70 and 21/71 are ODVA-specific AC Drive profiles.
For guidelines in telegram selection, please refer to the Device-
Net Operating Instructions.
Note that a change to this parameter will be executed immedi-
ately.
[0] Instance 100/150
[1] Instance 101/151
[2] Instance 20/70
[3] Instance 21/71
10-11 Process Data Config Write
Option: Function:
[0 ]
*
None
3-02 Minimum refer-
ence
3-03 Maximum refer-
ence
3-12 Catch up/slow
down value
3-41 Ramp 1 ramp up
time
3-42 Ramp 1 ramp
down time
3-51 Ramp 2 ramp up
time
3-52 Ramp 2 ramp
down time
3-80 Jog ramp time
3-81 Quick stop ramp
time
FC 100/ 200/ 300 DeviceNet 6. Parameters
MG.33.D3.02 - VLT
®
is a registered Danfoss trademark
59