EasyManua.ls Logo

Danfoss VLT Micro Drive FC 51 Series - Parameter Group 2: Brakes

Danfoss VLT Micro Drive FC 51 Series
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.3. Parameter Group 2: Brakes
4.3.1. 2-** Brakes
4.3.2. 2-0* DC-Brake
The purpose of DC-brake function is to brake a rotating motor by applying DC-current to the motor.
2-00 DC Hold Current
Range: Function:
This parameter either holds the motor (holding torque) or pre-heats the motor.
The parameter is active if
DC Hold
has been selected in either par. 1-72
Start Function
or par. 1-80
Function at
Stop
.
50%
*
[0 - 100%]
Enter a value for holding current as a percentage of the rated motor current set in par. 1-24
Motor Current
.
100% DC holding current corresponds to I
M,N
.
NB!
Avoid 100% current too long as it may overheat the motor.
2-01 DC Brake Current
Range: Function:
50 %
*
[0 - 150%]
Set DC-current needed to brake rotating motor.
Activate DC-brake in one of the four following ways:
1. DC-brake command, see par. 5-1* choice [5]
2. DC Cut-in function, see par. 2-04
3. DC-brake selected as start function, see par. 1-72
4. DC-brake in connection with
Flying Start
, par. 1-73.
2-02 DC-Braking Time
Range: Function:
DC-braking time defines the period during which
DC-brake current
is applied to the motor.
10.0 s
*
[0.0 - 60 s]
Set the time DC-braking current, set in par. 2-01, must be applied.
NB!
If DC-brake is activated as start function, DC-brake time is defined by
start delay time
.
2-04 DC-Brake Cut-in Speed
Range: Function:
0.0 Hz
*
[0.0 - 400.0 Hz]
Set DC-brake cut-in speed to activate DC braking current, set in par. 2-01, when ramping down.
When set to 0 the function is off.
4. Parameter Descriptions VLT
p
Micro Drive FC 51
22
MG.02.C4.02 - VLT
p
is a registered Danfoss trademark
4

Other manuals for Danfoss VLT Micro Drive FC 51 Series

Related product manuals