4.9. Parameter Group 8: Communication
4.9.1. 8-** Communication
Parameter group for configuring communication.
4.9.2. 8-0* General Settings
Use this parameter group for configuring the general settings for communication.
8-01 Control Site
Option: Function:
[0]
*
Digital and Control
Word
Use both digital input and control word as control.
[1] Digital Only Use digital input as control.
[2] Control Word Only Use control word only as control.
NB!
The setting in this parameter overrules settings in par. 8-50 to 8-56.
8-02 Control Word Source
Option: Function:
[0] None Function is inactive
[1]
*
FC RS485 Monitoring control word source is done via serial communication port RS485.
8-03 Control Word Timeout Time
Range: Function:
1.0 s
*
[0.1 - 6500 s]
Enter time to pass before control word timeout function (par. 8-04) must be carried out.
8-04 Control Word Timeout Function
Option: Function:
Select the action to be taken in case of a timeout.
[0]
*
Off No function.
[1] Freeze Output Freeze output until communication resumes.
[2] Stop Stop with auto restart when communication resumes.
[3] Jogging Run motor at jog frequency until communication resumes.
[4] Max. Speed Run motor at max. frequency until communication resumes.
[5] Stop and Trip Stop motor, then reset frequency converter in order to restart either via LCP or digital input.
8-06 Reset Control Word Timeout
Option: Function:
Resetting the control word timeout will remove any timeout function.
[0]
*
No Function Control word timeout is not reset.
[1] Do Reset Control word timeout is reset, and parameter goes into
No Function
state.
4.9.3. 8-3* FC Port Settings
Parameters for configuring the FC Port.
4. Parameter Descriptions VLT
p
Micro Drive FC 51
44
MG.02.C4.02 - VLT
p
is a registered Danfoss trademark
4

Other manuals for Danfoss VLT Micro Drive FC 51 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 Series and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive FC 51 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals