EasyManuals Logo
Home>Danfoss>Media Converter>VLT Micro Drive FC 51 Series

Danfoss VLT Micro Drive FC 51 Series Programming Guide

Danfoss VLT Micro Drive FC 51 Series
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
However, there are exceptions if par. 3-00 is set to
Min - Max
, [0].
Example 1:
Par. 3-02 is set to 20 and par. 3-03 is set to 50. In this case 0% = 0 and 100% = 50.
Example 2:
Par. 3-02 is set to -70 and par. 3-03 is set to 50. In this case 0% = 0 and 100% = 70.
3-11 Jog Speed [Hz]
Range: Function:
Jog speed is a fixed output speed and overrules the selected reference speed, see par. 5-1* selection [14].
If the motor is stopped while in jog mode, the jog signal acts as a start signal.
Removing the jog signal makes the motor run according to the selected configuration.
5.0 Hz [0.0 - 400.0 Hz] Select speed to function as jog speed.
3-12 Catch Up/Slow Down Value
Range: Function:
0%
*
[0 - 100%]
The
Catch-up/Slowdown function
is activated by an input command (see par. 5-1*, choice [28]/[29]). If the
command is active, the Catch-up/Slowdown value (in %) is added to the reference function as follows:
Reference
=
Reference
+
Reference
×
Catchup Slowdown
100
Reference
=
Reference
ì
Reference
×
Catchup Slowdown
100
When the input command is inactivated, the reference returns to its original value ie. Reference = Reference +
0.
3-14 Preset Relative Reference
Range: Function:
0.00% [-100.00 - 100.00%] Define fixed value in % to be added to variable value defined in par. 3-18,
Relative Scaling Reference Source
.
The sum of fixed and variable values (labelled Y in illustration below) is multiplied with actual reference (labelled
X in illustation). This product is added to actual reference
X
+
X
×
Y
100
3-15 Reference 1 Source
Option: Function:
Par. 3-15, 3-16 and 3-17 define up to three different reference signals. The sum of these reference signals
defines the actual reference.
[0] No Function No reference signal is defined.
[1]
*
Analog Input 53 Use signals from analog input 53 as reference, see par. 6-1*.
[2] Analog Input 60 Use signals from analog input 60 as reference, see par. 6-2*.
[8] Pulse input 33 Use signals from pulse input as reference, see par. 5-5*.
[11] Local Bus Reference Use signals from local bus as reference, see par. 8-9*.
[21] LCP Potentiometer Use signals from LCP potentiometer as reference, see par. 6-8*.
3-16 Reference 2 Source
Option: Function:
See Par. 3-15 for description.
[0] No Function No reference signal is defined.
[1] Analog Input 53 Use signals from analog input 53 as reference.
4. Parameter Descriptions VLT
p
Micro Drive FC 51
26
MG.02.C4.02 - VLT
p
is a registered Danfoss trademark
4

Other manuals for Danfoss VLT Micro Drive FC 51 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Micro Drive FC 51 Series and is the answer not in the manual?

Danfoss VLT Micro Drive FC 51 Series Specifications

General IconGeneral
BrandDanfoss
ModelVLT Micro Drive FC 51 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals