[1] On SLC is active.
13-01 Start Event
Option: Function:
Select input to activate Smart Logic Control.
[0] False Enters
False
in logic rule.
[1] True Enters
True
in logic rule.
[2] Running See par. 5-4* [5] for description.
[3] InRange See par. 5-4* [7] for description.
[4] OnReference See par. 5-4* [8] for description.
[7] Out of Current Range See par. 5-4* [12] for description.
[8] BelowILow See par. 5-4* [13] for description.
[9] AboveIHigh See par. 5-4* [14] for description.
[16] ThermalWarning See par. 5-4* [21] for description.
[17] MainsOutOfRange Mains voltage is outside the specified voltage range.
[18] Reversing See par. 5-4* [25] for description.
[19] Warning A warning is active.
[20] Alarm_Trip A trip alarm is active.
[21] Alarm_TripLock A trip lock alarm is active.
[22] Comparator 0 Use result of comparator 0 in logic rule.
[23] Comparator 1 Use result of comparator 1 in logic rule.
[24] Comparator 2 Use result of comparator 2 in logic rule.
[25] Comparator 3 Use result of comparator 3 in logic rule.
[26] LogicRule 0 Use result of logic rule 0 in logic rule.
[27] LogicRule 1 Use result of logic rule 1 in logic rule.
[28] LogicRule 2 Use result of logic rule 2 in logic rule.
[29] LogicRule 3 Use result of logic rule 3 in logic rule.
[33] DigitalInput_18 Use value of DI 18 in logic rule.
[34] DigitalInput_19 Use value of DI 19 in logic rule.
[35] DigitalInput_27 Use value of DI 27 in logic rule.
[36] DigitalInput_29 Use value of DI 29 in logic rule.
[38] DigitalInput_33
[39]
*
StartCommand This event is
True
, if frequency converter is started by any means (digital input or other).
[40] DriveStopped This event is
True
, if frequency converter is stopped or coasted by any means (digital input or other).
13-02 Stop Event
Option: Function:
Select input to activate Smart Logic Control.
[0] False Enters
False
in logic rule.
[1] True Enters
True
in logic rule.
[2] Running See par. 5-4* [5] for description.
[3] InRange See par. 5-4* [7] for description.
[4] OnReference See par. 5-4* [8] for description.
[7] Out of Current Range See par. 5-4* [12] for description.
[8] BelowILow See par. 5-4* [13] for description.
[9] AboveIHigh See par. 5-4* [14] for description.
[16] ThermalWarning See par. 5-4* [21] for description.
[17] MainsOutOfRange Mains voltage is outside the specified voltage range.
VLT
p
Micro Drive FC 51 4. Parameter Descriptions
MG.02.C4.02 - VLT
p
is a registered Danfoss trademark
49
4