[6] AutoReset 6 Performs six automatic resets after tripping.
[7] AutoReset 7 Performs seven automatic resets after tripping.
[8] AutoReset 8 Performs eight automatic resets after tripping.
[9] AutoReset 9 Performs nine automatic resets after tripping.
[10] AutoReset 10 Performs ten automatic resets after tripping.
[11] AutoReset 15 Performs fifteen automatic resets after tripping.
[12] AutoReset 20 Performs twenty automatic resets after tripping.
[13] Infinite auto reset Performs an infinite number of automatic resets after tripping.
Motor may start without warning.
14-21 Automatic Restart Time
Range: Function:
10 s
*
[0 - 600 s]
Enter time interval from trip to start of automatic reset function. This parameter is active when par. 14-20,
Reset
Mode
, is set to
Automatic Reset
[1] - [13].
14-22 Operation Mode
Option: Function:
Use this parameter for specifying normal operation or to initialize all parameters, except par. 15-03, 15-04 and
15-05.
[0]
*
Normal Operation Frequency converter runs normal operation.
[2] Initialization Resets all parameters to default settings, except for 15-03, 15-04 and 15-05. Frequency converter resets during
next power-up.
Par. 14-22 also reverts to default setting
Normal Operation
[0].
4.11.5. 14-4* Energy Optimizing
These parameters are for adjusting the energy optimization level in both Variable Torque (VT) and Automatic Energy Optimization (AEO) modes.
14-41 AEOMinimum Magnetization
Range: Function:
66%
*
[40 - 75%]
Enter the minimum allowable magnetization for AEO. Selecting a low value reduces energy loss in the motor, but
may also reduce resistance to sudden load changes.
4. Parameter Descriptions VLT
p
Micro Drive FC 51
56