EasyManua.ls Logo

Danfoss VLT5000 SyncPos - Page 137

Danfoss VLT5000 SyncPos
236 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programmable SyncPos motion controller
MG.10.J8.02 – VLT is a registered Danfoss trade mark
136
Software Reference
OUTAN
The OUTAN command can set VLT bus reference
(speed or torque reference depending on setting of
VLT parameter 100).
NB!
The command MOTOR OFF must be execu-
ted previously. Thus, monitoring of the position
error is no longer active.
With OUTAN it is also possible to turn off the con-
troller in OPEN LOOP using MOTOR OFF and to
operate the VLT without return as a pure frequency
converter. In this manner you can use SyncPos to
directly output set values, to read inputs, etc.
Summary
sets speed reference
Syntax
OUTAN v
Parameter
v = speed reference
range: –0X4000 … 0X4000 = –100 % … 100 %
NB!
Remember that with older versions a different
scale may exist.
Command group
I/O
Cross Index
MOTOR OFF
Chapter input/output terminal; VLT5000 manual
Syntax-Example
MOTOR OFF
OUTAN 0X2000 /* set speed reference 50 % */
OUTB
With the OUTB command the condition of the digital
outputs can be changed byte-by-byte. The byte value
transferred determines the condition of the individual
outputs. The bit with the lowest value in the byte cor-
responds to the set condition of output 1.
Summary
Alteration of the condition of a digital output byte
Syntax
OUTB n v
Parameter
n = output byte (0 = O1 ... O8)
v = value (0 ... 255)
NB!
After switching on the system, all outputs are
OFF. Outputs which have pre-defined func-
tions according to the I/O parameter settings, will
also be influenced by the OUTB command! The
actual output status remains as it is even after pro-
gram end or program abort. Output circuit and maxi-
mum load current
see chapter input/output terminal.
Command group
I/O
Cross Index
OUT, IN, INB
Syntax-Example
OUTB 0 10
/* switch through outputs 2 and 4, disable other
outputs */
OUTB 0 245
/* disable outputs 2 and 4, switch through all other
outputs */
OUTB 0 128
/* switch through output 8 only, disable others */
Program sample
OUTB_01.M

Table of Contents

Related product manuals