DKG-109 User Manual V-27 (23.08.2013)
- 28 -
Program Group: Controller Configuration
Parameter Definition,
(Password Level)
This parameter is used to set LCD contrast. Adjust
for the best viewing angle.
0: English language selected.
1: Turkish language selected. This language may
depend on the country where the unit is intended to
be used.
2: Chinese language selected
3: The unit will ask for manual language selection at
power-on.
0: Use primary voltage/frequency limits
1: Use secondary voltage/frequency limits
(2) Line-to-Line Voltages
0: Display Line to Neutral voltages as default
1: Display Line to Line voltages as default
(1) Genset Default Display
This parameter selects the screen which is displayed
during genset on load operation.
0: screen 3 electrical, large characters
1: screen 4 engine parameters, large characters
2: screen 5 maximum information, small characters
3: screen 6 analog power-meter
Details of each screen are explained in chapter 3.2
1: Engine control (no alternator
This parameter defines the delay after the engine
runs and before the fault monitoring is enabled.
This is the period during which the ALARM relay is
active. If the period is set to 0, this will mean that the
period is unlimited.
(1) Intermittent Alarm Relay
1: intermittent (turns on and off every second)
(2) Charge Alternator
Shutdown
0: The charge input generates CHARGE FAIL
warning, and does not stop the engine.
1: The charge input generates CHARGE FAIL alarm,
and stops the engine.
(1) Emergency Backup
Operation
0: In RUN mode, the load will not be transferred to
the genset even if the mains fail.
1: In RUN mode, the load will be transferred to the
genset if the mains fail.
(2) Enable Delayed Simulate
Mains
0: Delayed simulate mains not enabled
1: Delayed simulate mains enabled