Bit No. Logic Function
0 "BELOW BARGRAPH" VIOLATION OUTPUT
Terminal 0 will be at a
Logic 1
(0 V-DC) level whenever
the reading of Channel 5 is less than the current "LEP"
value for that channel.
1 "LOW LOW" VIOLATION OUTPUT
Terminal 1 will be at a
Logic 1
(0 V-DC) level whenever
the reading of Channel 5 is less than the current "LLL"
value for that channel and greater than or equal to the
current "LEP" value.
2 "LOW" VIOLATION OUTPUT
Terminal 2 will be at a
Logic 1
(0 V-DC) level whenever
the reading of Channel 5 is less than the current "LOL"
value for that channel and greater than or equal to the
current "LLL" value.
3 "OK" (NO VIOLATION) OUTPUT
Terminal 3 will be at a
Logic 1
(0 V-DC) level whenever
the reading of Channel 5 is greater than or equal to the
current "LOL" limit value and less than or equal to the
current "HIL" limit value for that channel.
4 "HIGH" VIOLATION OUTPUT
Terminal 4 will be at a
Logic 1
(0 V-DC) level whenever
the reading of Channel 5 is greater than the current "HIL"
value for that channel and less than or equal to the
current "HHH" value.
5 "HIGH HIGH" VIOLATION OUTPUT
Terminal 5 will be at a
Logic 1
(0 V-DC) level whenever
the reading of Channel 5 is greater than the current
"HHH" value for that channel and less than or equal to
the current "HEP" value.
6 "ABOVE BARGRAPH" VIOLATION OUTPUT
Terminal 6 will be at a
Logic 1
(0 V-DC) level whenever
the reading of Channel 5 is greater than the current
"HEP" value for that channel.
1.12
Standard Logic Configuration 1.e