Setup of a controller with analogue option and AVR option
Sequence
2781
Select analogue
for GOV
2783
Select analogue
for AVR
5980
Select Transducer
66 for GOV
5990
Select Transducer
71 for AVR
Start the DG in
MAN Mode
Is the freq.
the same
as nom.
2550
Increase or
decrease
Is the volt.
same as
nom.
2670
Increase or
decrease
2740
Adjust the time
in this parameter
Switch to Semi-
Auto mode
2510
Adjust Kp Ti and
Td
Copy the settings
from 2510 to 2530,
2540 and 2040
2640
Adjust Kp Ti and
Td
Copy the settings
from 2640 to 2650
and 2660
End
No
No
Yes
Yes
For further information, please refer to the General Guidelines for Commissioning.