Setup of a controller with relay and AVR option
Sequence
2781
Select relay
for GOV
2783
Select relay
for AVR
2723
Select Incr. Relay
for AVR
2724
Select Decr. relay
for AVR
2603
Select Incr. relay
for GOV
Is the freq.
the same
as nom.
Adjust the
frekquency on the
Speed gov.
Is the volt.
same as
nom.
Adjust the voltage
on the AVR
2740
Adjust the time
in this parameter
2601
Decrease GOV on
time to minimum
2720 Decrease
AVR on time to
minimum
Switch to Semi
Auto mode
2570
Adjust Kp
Copy the setting
from 2690 to 2700,
2710
End
No
No
Yes
Yes
2604
Select Decr. relay
for GOV
Start the DG in
MAN Mode
Copy the setting
from 2570 to 2580,
2590,2050
2690
Adjust Kp
For further information, please refer to the General Guidelines for Commissioning.