Deif AGC-4 - Page 26

Deif AGC-4
26 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setup of a controller with EIC for GOV control and analogue for AVR control
Start
2781
Select EIC for
GOV
2783
Select analogue
for AVR
5990
Select transducer
66 or 71
Start the DG in
MAN Mode
2550
Increase or
decrease
2670
Increase or
decrease
2740
Adjust the time
in this parameter
Switch to SEMI-
auto mode
2510 Adjust Kp
and Ti
Copy the settings
from 2510 to 2530,
2540 and 2040
2640
Adjust Kp and Ti
Copy the settings
from 2640 to 2650
and 2660
End
No
No
Yes
Yes
Is the HZ the
same as nom?
Is the U the same
as nom?
For further information, please check the following literature:
AGC Designer’s Reference Handbook
AGC Installation Instructions
AGC Operator’s Manual
AGC-4 quick start guide 4189340689 UK
Display push-buttons and LEDs
DEIF A/S Page 26 of 26