3. Mounting
3.1 CGC 200 mounting
Protect the controller terminals from static discharge during installation.
3.1.1 Mounting of the unit
The unit is designed for mounting by means of two fixing clamps, which are included at delivery.
3.1.2 Unit dimensions and panel cutout
The unit is designed for mounting in the panel front.
In order to ensure optimum mounting, the panel door must be cut out according to the following measure-
ments:
H × W = 68.00 × 80.00 +0.40 mm and -0.00 mm
H × W = 2.68" × 3.15" + 0.02" and -0.00"
78.50
66.50
94.75
82.75
43.00
8
7
6
5
4
3
2
1
11
12
13
14
15
10
9Gens L
Gens N
Fuel Output
Start Output
Config. Output 1
USB
Config. Output 3
MPU Input
Input 4
Emergency Stop
Input 3
Input 2
Input 1
-
+
Power Supply 8-35 V ,2 A
Relay Outputs 30 V ,1 A
D002-1112
Config. Output 2
Input 5
36.00
0.3 Nm
3.1.3 Tightening torques
Unit panel door mounting: 0.3 Nm (see diagram in "Unit dimensions and panel cutout")
Plug connections (terminals): 0.5 Nm
CGC 200 installation and commissioning
instructions 4189340806 UK
Mounting