Table 2: Configurable input functions
Configurable input function Value in the controller Digital input*
Not used 0
Remote start/stop 6
Low fuel level warning 5
Low oil pressure warning 8
Low oil pressure shutdown 2
High oil temperature warning 7
High oil temperature shutdown 1
High coolant temperature shutdown 9
Auxiliary alarm shutdown (Emergency stop) 4
*You can fill in the number of the corresponding digital input configured for this function in your system.
4.2 Wiring
4.2.1 Checking the wiring
You can use the utility software during commissioning to check the wiring. You can connect the CGC 200 to a
PC using a USB cable and check whether the operating values are as expected. You can use P43 and P44
to calibrate the genset and battery voltage measurements. See the Designer's handbook for more informa-
tion. Voltage calibration is only available through the utility software.
You can also use the CGC 200 front panel to monitor operating values during commissioning.
4.3 Commissioning using the Utility Software
4.3.1 Installing the Utility Software
The Utility Software (USW) must be installed on a PC (either a laptop or a desktop computer) running the
Microsoft Windows operating system.
Do not connect the controller to the PC (using the USB cable) before the software is installed.
Microsoft Windows creates an incorrect USB driver if the controller is connected before the
software is installed. If you have this problem, you need to find the correct USB driver in the
software installation folder and install it.
The USW is normally downloaded from DEIF via the internet.
To download the Utility Software:
1. Open www.deif.com in a browser.
2. Click Documentation and Software in the top menu.
CGC 200 installation and commissioning
instructions 4189340806 UK
Commissioning
DEIF A/S Page 16 of 32