The parameters used by CGC 200 that can only be viewed and changed from the utility software are listed in
the table below.
Param-
eter
number
Parameter name Range De-
fault
value
Value
chos-
en*
Description
43 Calibrate AC voltage 700 to 1300 1000 See the Designer's handbook
for more information
44 Calibrate battery voltage 700 to 1300 1000 See the Designer's handbook
for more information
45 Running hours offset
(9999-19998)
0 to 9999
hours
0 Additional offset for the genset's
running time timer
46 Running hours offset
(0-9999)
0 to 9999
hours
0 Additional offset for the genset's
running time timer
47 Running minutes offset 0 to 59 mi-
nutes
0 Additional offset for the genset's
running time timer
48 Running seconds offset 0 to 59 s 0 Additional offset for the genset's
running time timer
49 Start attempts offset
(9999-19998)
0 to 9999 0 Additional offset for the genset's
start attempts counter
50 Start attempts offset
(0-9999)
0 to 9999 0 Additional offset for the genset's
start attempts counter
*You can fill in the values chosen for your system.
Table 1: Configurable output functions
Configurable output function Value in the controller Config. output*
Not used 0
Common alarm 1
Stop coil 2
Pre-heat 4
Idle speed 3
Close breaker 6
*You can fill in the number of the corresponding relay configured for this function in your system.
CGC 200 installation and commissioning
instructions 4189340806 UK
Commissioning