Param-
eter
num-
ber
Parameter
name
Range De-
fault
value
Value
chos-
en*
Description
P40 Running detect. 0 to 2 2 0: RPM
1: Genset frequency
2: RPM and frequency (running detec-
tion is present when the value required
to remove the starter is met for either
engine speed (see P41) or genset fre-
quency (see P42))
For RPM, P13 and P41 must be de-
fined.
For frequency, P42 must be defined.
P41 Remove starter
RPM
0 to 3000
RPM
360 Minimum engine speed required for re-
moval of the starter and running detec-
tion
P42 Remove starter
Hz
10.0 to 30.0
Hz
14.0 Minimum genset frequency required for
removal of the starter and running de-
tection
*You can fill in the values chosen for your system.
CGC 200 installation and commissioning
instructions 4189340806 UK
Commissioning
DEIF A/S Page 14 of 32