Common
Switch
0 V
dc
Digital input
The digital inputs require DC voltage. AC voltage will damage the controller.
2.2.4 List of terminal connections
The power supply, inputs and outputs are connected to the CGC 200 terminals. CGC 200 also has a USB B-
socket for connecting to a PC. The terminal connections are listed in the following table.
No. Name Type Details
1 + Power supply + 8 to 35 V
dc
2 - Power supply - Ground
3 MPU Input RPM input Magnetic pickup, or tacho generator
4 Input 1 Digital input Coolant temperature switch, or configura-
ble
5 Input 2 Digital input Low oil pressure switch, or configurable
6 Emergency Stop Input
3
Digital input Emergency stop input (Auxiliary)
7 Input 4 Digital input Remote start, or configurable
8 Input 5 Digital input Configurable
9 Gens L Generator voltage L1 Generator voltage measurement
10 Gens N Generator neutral Generator voltage measurement
11 Fuel Output Relay output (normally open) Run coil
12 Start Output Relay output (normally open) Starter (crank)
13 Config. Output1 Relay output (normally open) Configurable
14 Config. Output2 Relay output (normally open) Configurable
15 Config. Output3 Relay output (normally open) Configurable
USB USB Service Port USB B female connection For connection to a PC