PPM Installation Instructions
DEIF A/S Page 56 of 69
CAN ID configuration on display unit
The CANbus ID no. for the display unit of generator 1 (Master) has to be changed from ID no. 0
(default) to ID no. 1. To do this, press the three buttons left, up and right at the same time.
Then press the up button to change the ID no. from 0 to 1.
Acknowledge by pressing 'ENTER'. The display will then automatically reset.