Bump: 20 g, 16 msec, half sine
To IEC 60255-21-2 (class 2)
Material: All plastic materials are self-extinguishing according to UL94 (V1)
Plug connections: AC current: 0.2-4.0 mm
2
stranded wire (UL/cUL Listed: AWG 18)
AC voltage: 0.2-2.5 mm
2
stranded wire (UL/cUL Listed: AWG 20)
Relays: (UL/cUL Listed: AWG 22)
Other: 2.5 mm
2
multi stranded (UL/cUL Listed: AWG 24)
Display: 9-pole Sub-D female
PC: USB A-B
Ethernet: RJ45
Approvals: The PPM is approved by the major classification societies. Contact
DEIF for details
UL and cUL
UL markings: Wiring:
Use 60/75°C copper conductors only
Mounting:
For use on a flat surface of type 1 enclosure
Installation:
To be installed in accordance with the NEC (US) or the CEC (Canada)
Governors: Multi-line 2 interfaces to all governors, including GAC, Barber-Colman,
Woodward and Cummins
See interfacing guide at www.deif.com
Weight: Main unit: 1.5 kg (3.40 lbs.)
J1, cable 3 m: 0.2 kg (0.45 lbs.)
Option J2: 0.4 kg (0.90 lbs.)
Option J7: 0.2 kg (0.45 lbs.)
Display: 0.4 kg (0.90 lbs.)
Protection: Unit: IP20
Display: IP52 (IP54 with gasket, option L)
(UL/cUL Listed: Type Complete Device, Open Type)
To IEC 529 and EN 60529