Delem
V1204, 2.14
Parameter 03:
Scale factor
Range : 0.001 - 999.999
Unit : pulse/mm
Default : 100.000
Function
Sets the scaling between encoder pulses and millimeters. The encoder gives an exact number
of pulses over a mm displacement. This value must be programmed here.
The value can be calculated by the formula:
F = NP / SPP
in which:
- NP = Number of encoder pulses per revolution of the spindle
- SPP = Spindle pitch in mm
Example:
- number of encoder pulses: 100 pulse/rev.
- spindle pitch: 10 mm/rev.
results in F= 100 / 10 = 10 pulse/mm
Parameter 04:
Decimal point position
Range : 0 - 3
Unit : -
Default : 1
Function
0 = 1 mm / 0.1 inch resolution
1 = 0.1 mm / 0.01 inch resolution
2 = 0.01 mm / 0.001 inch resolution
Parameter 05:
Maximum backgauge position
Range : 0 - 9999
Unit : mm
Default : 9999
Function
Maximum backgauge position. The axis will never be controlled to a higher position than
programmed here.