Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous
contamination. If the level of particulates or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility
of the customer.
表. 30: Particulate contamination specifications
Particulate contamination Specifications
Air filtration Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
注: This condition applies only to data center
environments. Air filtration requirements do not apply to IT
equipment designed to be used outside a data center, in
environments such as an office or factory floor.
注: Air entering the data center must have MERV11 or
MERV13 filtration.
Conductive dust Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
注: This condition applies to data center and non-data
center environments.
Corrosive dust
● Air must be free of corrosive dust.
● Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
注: This condition applies to data center and non-data
center environments.
表. 31: Gaseous contamination specifications
Gaseous contamination Specifications
Copper coupon corrosion rate <300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
Silver coupon corrosion rate <200 Å/month as defined by AHSRAE TC9.9.
注: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Identifier GUID-BC6F1127-DB18-4A68-A659-9A814E04C847
Version 5
Status Translation Validated
标准操作温度
表
. 32: 标准操作温度规格
标准操作温度 规格
温度范围(在低于海拔 950 米或 3117 英尺时) 在设备无直接光照的情况下,10°C 至 35°C(50°F 至
95°F)。
注: 在配备 8 个 2.5 英寸驱动器、2–PCI 插槽机箱和 75 W
单宽活动 GPU 的系统中,最多支持 145 W 22 内核的处理
器。
36 技术规格