42
Amplon RT Series
6.5 Battery Test
Battery test can only be executed in on-line mode and in ECO mode.
1. For automatic regular battery test, you must install the UPSentry 2012 software
LQFOXGHGLQWKHSURYLGHG&'RUFRQ¿JXUHWKH6103FDUGRSWLRQDORU0RG%XV
card (optional).
2. For manual battery test, please press and hold the
ON
button for 3 seconds,
release it after you hear one beep, and the UPS will transfer to run in battery
mode and perform a 10-second battery test.
6.6 Alarm
No. Condition Alarm
1 Battery Mode The audible alarm beeps once every 2 seconds.
2 Low Battery The audible alarm beeps once every 0.5 second.
3
Battery Missing/
Weak Battery/ Battery
Replacement
The audible alarm beeps once every 2 seconds.
4 Overload The audible alarm beeps once every 2 seconds.
5 Fault
The audible alarm beeps once for 5 seconds
when the UPS detects an internal fault.
NOTE :
After reconnecting or replacing the batteries, it might take a while for the UPS
to switch off the alarm automatically. If, after a period of time, the audible
alarm still exists, the user must manually initiate a battery test (press and
hold the
ON
button for 3 seconds and release it after you hear one beep) to
clear the alarm.
6.7 De-rating Power
When the input voltage range is between 100Vac and 160Vac, the UPS’s load
capacity will decrease. This function provides a wider operating power voltage
range.