Chapter 12 Troubleshooting
12-27
12_
Error
code
Description
CPU
status
ERROR LED indicator status
ON
Blinking
fast
Blinking
normally
Blinking
slowly
OFF
0052
The memories in the latched auxiliary relays are
abnormal.
Continue V
0054
The latched counters are abnormal.
Continue
V
0055 The latched 32-bit counters are abnormal. Continue V
0056 The latched special auxiliary relay is abnormal. Continue V
0059
The latched data registers are abnormal.
Continue
V
005D
The CPU module does not detect a memory card.
Continue
V
005E
The memory card is initialized incorrectly.
Continue
V
0063
An error occurs when data is written to the memory
card.
Continue V
0064 A file in the memory card cannot be read. Continue V
0070
The actual placement of the function cards is not
consistent with the settings.
Stop V
0102 The interrupt number exceeds the range. Stop V
0202 The MC instruction exceeds the range. Stop V
0302 The MCR instruction exceeds the range. Stop V
0D03
The operands used in DHSCS are not used
properly.
Stop V
0E05
The operands HCXXX used in DCNT are not used
properly.
Stop V
1300
-
130F
Errors occurred in the remote modules Continue V
1402
The arrangement of the I/O modules is not
consistent with the settings.
Stop V
140B
Number of communication modules exceeds the
limit of four.
Stop V
140D
Number of extension modules exceeds the limit of
32.
Stop V
140E
Number of remote modules exceeds the limit of
eight on the right side of the CPU module.
Stop V
1500 Connection lost in the remote modules Continue V
1502
-
150F
Errors occurred in the remote modules Continue V
1600
The ID of the extension module exceeds the range.
Stop
V
1601 The ID of the extension module cannot be set. Stop V
1602 The ID of the extension module is duplicated. Stop V
1603
The extension module cannot be operated.
Stop
V
1604
Extension module communication timeout
Stop
V
1605
Hardware failure
Stop
V
1606
Errors on the communication module function card
Stop