Error
code
Description
CPU
status
ERROR LED indicator status
ON
Blinking
fast
Blinking
normally
Blinking
slowly
OFF
1607
The external voltage is abnormal.
Stop
V
1608
The Internal factory calibration or the CJC is
abnormal.
Stop V
1609
-
160F
Reserved (Error codes for the extension modules) Stop V
1800
-
180F
Errors occurred in the extension modules Continue V
1900
-
191C
Heartbeat errors occurred in the slave of the Delta
ASD-A2 control.
Continue V
1950
The initialization of the Delta ASD-A2 control has
not yet been completed, the CANopen instructions
cannot be executed.
Continue V
2001
Not
using the FCOMP card or not in the right mode
for the ASDA-
A2 while using the CANopen
communication instruction.
Continue V
2003
The device used in the program excee
ds the device
range or is illegal.
Continue V
200A Invalid instruction Stop V
200B
The operand n or the other constant operands K/H
exceed the range.
Continue V
200C
The operands overlap.
Continue
V
200D
The binary to binary-coded decimal conversion
is
incorrect.
Continue V
200E
The string does not end with 00.
Continue
V
2012
Incorrect division operation
Continue
V
2013
The value exceeds the range of values which can
be represented by the floating-point numbers.
Continue V
2014
T
he task designated by the TKON or YKOFF
instruction is incorrect, or exceeds the range.
Continue V
2017
The instruction BREAK is written outside of the
FOR-NEXT loop.
Continue V
2027
No such position planning table number or the
format is incorrect.
Continue V
2028
The high speed output instruction is being
executed. Only one instruction can be executed at
a time.
Continue V
2030
During the execution of CSFO instruction, the
output frequency exceeds the upper limit.
Continue V
2031
During the execution of CSFO instruciotn, when
the output frequency is set to 0, but even after 2
seconds, the output is still not complete.
Continue V
6004
The IP address filter is set incorrectly.
Continue