EasyManuals Logo

Delta AS16AP11P-A User Manual

Delta AS16AP11P-A
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #424 background imageLoading...
Page #424 background image
AS Series Operation Manual
12-30
_12
Error
code
Description
CPU
status
ERROR LED indicator status
ON
Blinking
fast
Blinking
normally
Blinking
slowly
OFF
7011
The device communication function code in
COM1
is incorrect.
Continue V
7012
The device communication address used in
COM1
is incorrect.
Continue V
7013
The device used in COM1
exceeds the device
range.
Continue V
7014
The device length of the communication
data in
COM1 exceeds the limit.
Continue V
7017
The device checksum for the co
mmunication serial
port of COM1 is incorrect.
Continue V
7021
The device communication function code in COM2
is incorrect.
Continue V
7022
The device communication address used in COM2
is incorrect.
Continue V
7023
The device used in COM2 ex
ceeds the device
range.
Continue V
7024
The device length of the communication
data in
COM2 exceeds the limit.
Continue V
7027
The device checksum
for the communication serial
port of COM2 is incorrect.
Continue V
7031
The device communication
function code in
Ethernet is incorrect.
Continue V
7032
The device communication address
used in
Ethernet is incorrect.
Continue V
7033
The device used in Ethernet
exceeds the device
range.
Continue V
7034
The device length of the communication data in
Ethernet exceeds the limit.
Continue V
7037
The device checksum
for the communication serial
port of Ethernet is incorrect.
Continue V
7041
The device communication function code in USB
is
incorrect.
Continue V
7042
The device communication address used in USB
is
incorrect.
Continue V
7043
The device used in USB exceeds the device range.
Continue
V
7044
The device length of the communication data in
USB exceeds the limit.
Continue V
7047
The device checksum for t
he communication serial
port of USB is incorrect.
Continue V
70B1
The device communication
function code in function
card 1 is incorrect.
Continue V
70B2
The device communication address
used in function
card 1 is incorrect.
Continue V
70B3
The device used in function card 1 exceeds
the
device range.
Continue V

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta AS16AP11P-A and is the answer not in the manual?

Delta AS16AP11P-A Specifications

General IconGeneral
BrandDelta
ModelAS16AP11P-A
CategoryControl Unit
LanguageEnglish