Chapter 8  Parameters  ASDA-A2 
8-48     Revision February, 2017 
 
Unit: 
% (full scale) 
 
Range: 
0 ~ 100 
 
Data Size: 
16-bit 
 
Format: 
Decimal 
 
Settings: 
Please refer to parameter P0-03 for the setting of analog output 
selection. 
For example: P0-03 = 0x00 (MON2 is the speed analog output) 
When the output voltage value of MON2 is V2: Motor speed = (Max. × 
V2/8) × P1-05/100 
 
P1-06    SFLT  Analog Speed Command (Low-pass Filter) 
Address: 010CH 
010DH 
 
Operational 
Interface: 
Panel / Software  Communication 
Related Section: 
6.3.3 
 
Default: 
0 
 
Control 
Mode: 
S 
 
Unit: 
ms 
 
Range: 
0 ~ 1000 (0: disable this function) 
 
Data Size: 
16-bit 
 
Format: 
Decimal 
 
Settings: 
0: Disabled 
 
P1-07    TFLT  Analog Torque Command (Low-pass Filter) 
Address: 010EH 
010FH 
 
Operational 
Interface: 
Panel / Software  Communication 
Related Section: 
6.4.3 
 
Default: 
0 
 
Control 
Mode: 
T 
 
Unit: 
ms 
 
Range: 
0 ~ 1000 (0: disable this function) 
 
Data Size: 
16-bit 
 
Format: 
Decimal 
 
Settings: 
0: Disabled