Danger of death or severe injuries from dangerous voltage
Dangerous voltages can be present at the DC connections of the
solar power inverter.
Never disconnect the PV modules when the solar power inverter is
under load. First switch off the grid connection so that the solar power
inverter cannot feed energy into the grid. Then open the DC
disconnector.
Secure the DC connections against being touched.
Danger of injury due to heavy weight
The solar power inverter is heavy (see “9.2 Technical data”).
Incorrect handling can lead to injuries.
The solar power inverter must be lifted and carried by two
people.
8.1 Decommissioning
1. Switch off the AC cable to be free of voltage.
2. Open the DC disconnector.
3. Remove all cables from the solar power inverter.
4. Unscrew the solar power inverter from the wall bracket.
5. Lift the solar power inverter from the wall bracket.
8.2 Packaging
Use the original packaging or packaging of the same quality.