EasyManua.ls Logo

Delta DPM-D510 - 2.1 Electrical Characteristics

Delta DPM-D510
57 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Delta Din- rail Power Meter DPM- D510 User Manual
2- 2
_2
2.1 Electrical Characteristics
Input
Voltage
Connection
1PH2W, 1 CT 3PH3W, Δ connection, 3 CT, 2 PT
1PH3W, 2 CT 3PH4W, Y connection, 3 CT, No PT
3PH3W, Δ connection, 3 CT, No PT 3PH4W, Y connection, 3 CT, 3 PT
3PH3W, Δ connection, 2 CT, No PT 3PH4W, Y connection, 2 CT, 3 PT
Rated Voltage
Line voltage
35 to 690 VAC (L-L)
Phase voltage
20 to 400 VAC (L-N)
MEASUREMENT CAT III
Y connection (3P4W)
400 Vac (line-to-neutral) / 690 Vac (line-to-line)
Δ connection (3P3W)
600 Vac (line-to-line)
Rated Current Nominal : 1 A / 5 A
Range of Current
Measurement
20mA ~ 6A*
Start Current 20mA
Frequency 50 / 60 Hz
Voltage Input OVERVOLTAGE CAT II
Power Operating range 100 ~ 240 VAC (maximum power: 4.6 W)
Frequency Operating frequency 50/60 Hz
Communication RS-485 port
Modbus-RTU
Baud rate 9600 / 19200 / 38400 bps
Mechanical
Characteristics
Dimension (W x H x D)
90 * 90 * 66.7 mm
IP Degree of Protection
IP20
Environment Ambient operating temperature
-20 °C ~ +60°C
-4°F ~ +140°F
Measurement Accuracy
Electric quantities
Voltage,
current
± 0.5%
Electric energy
Real ± 0.5%
Real power ± 0.5% Reactive ± 2%
Power factor ± 1% Real power ± 2%
Frequency ± 1% Reactive power ± 2%