On/ Off Settings
Setup Item Selectable Value Default Value
Energy Saving
Option 1*
1
: Enable/ Disable
Option 2: 1-15 mins (per step: 1 min)
Option 3: 100W-270W (per step: 10W)
Disable
Sleep Mode
Option 1: Enable/ Disable
Option 2: 10-120 mins
(per step: 10 mins)
Disable
Auto Restart
Enable/ Disable
Enable
Auto Start on AC
Enable/ Disable
Disable
NOTE:
*
1
In
Setting Menu
, the sub item
Option 1
under the item
Energy Saving
cannot be
changed.
Battery
Setup Item Selectable Value Default Value
Automatic Battery
Test
No test/ Daily/ Weekly/
Biweekly/ Monthly
No test
Deep Discharge
Test
20-90% (per step: 10%)
90%
Low Battery
Warning Capacity
0-95%
(per step: 5%)
10%
Warning of
Remaining Time
0-60 mins
(per step: 1 min)
2 mins
Runtime Limitation
Disable/ 1/ 2/ 3…./ 240
(per step: 1 min)
Disable
Internal Charging
Current
Not adjustable
External Battery
Type
*
1
Standard Battery Pack/
Customer Own Batt. Pack