Amplon RT Series
12
3.2 Multi-function Buttons
No.
Multi-
function
Button
Description
ON/ OFF
Button
The button has multiple functions. Please refer to the following for detailed
information.
1. Turn on
In standby/ bypass mode, press and hold the button for 3
seconds, and release it after you hear one beep. After that, the
UPS will run in on-line mode.
Cold start: When there is no AC input, press and hold the button
for 3 seconds, and release it after you hear one beep. After that,
the UPS will run in battery mode.
2. Turn off
In on-line mode, (1) press and hold the button for 3 seconds, (2)
release it after you hear one beep, (3) use the Scrolling UP or
Down button ( / ) to select ‘Yes’, and (4) press the Enter
button ( ) to confirm your selection. After that, the inverter will
be off and the UPS will transfer to run in standby or bypass
mode.
In battery mode, (1) press and hold the button for 3 seconds, (2)
release it after you hear one beep, (3) use the
Scrolling UP
or
Down
button ( / ) to select ‘
Yes
’, and (4) press the
Enter
button ( ) to confirm your selection. After that, the UPS will be
turned off.
In battery mode, press and hold the button for 3 seconds, and
release it after you hear one beep. After that, the UPS will turn
off its output.
3. Fault Clear
When the UPS is under a fault condition, press and hold the button for
3 seconds, and release it after you hear one beep. After that, the UPS
will try to clear the fault.
NOTE:
1. When the UPS clears the fault, it means that the buzzer/
warning message has been turned off. To eliminate the fault
detected, please refer to
Chapter 11: Troubleshooting
for
relevant solutions.
2. The function mentioned above is only applicable to the
condition when the UPS has a fault and the inverter is off.