41
Outlet Control
Setup items
Selectable Value-
Level 2
Selectable Value-
Level 3
Default
Outlets -
Group 1
Output Reboot
Duration
Disable/ 5/ 6/…/ 300
Seconds (per step: 1 sec)
Disable
Load Bank
Runtime Limitation
Disable/ 1/ 2/…/ 240 mins
(per step: 1 min)
Disable
Outlets -
Group 2
Output Reboot
Duration
Disable/ 5/ 6/…/ 300
Seconds (per step: 1 sec)
Disable
Load Bank
Runtime Limitation
Disable/ 1/ 2/…/
240 mins (per step: 1 min)
Disable
Dry Contact Settings
Setup Item Selectable Value Default Value
Dry Contact
1 - Input
Option 1*
1
: Disable/ ROO/ RPO/ Remote shutdown/
Forced bypass/ On generator
Option 2: 0-999s (per step: 1 sec)
Option 3: Normal open/ Normal close
ROO/ 10s
Dry Contact
2 - Output
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS OK/
Load protected/ Load powered/ General alarm/ Overload
alarm
On Batt.
Dry Contact
3 - Output
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS OK/
Load protected/ Load powered/ General alarm/ Overload
alarm
Low Batt.
Dry Contact
4 - Output
Disable/ On bat/ Low bat/ Bat fault/ Bypass/ UPS OK/
Load protected/ Load powered/ General alarm/ Overload
alarm
General Alarm
Remote Control
Option 1: REPO/ ROO
REPO/
NO
Option 2:
(For REPO) Normally Open/ Normally Closed
(For ROO) Delay Time 0s ~ 999s (per step: 1s)
DB9 - Manual
Bypass
Enable/ Disable
Disable
NOTE:
*
1
For detailed information about
Option 1
, please contact service personnel.