Chapter 8 Optional Cards |CFP2000 Series
8-11
Environment
Noise immunity
ESD (IEC 61800-5-1, IEC 61000-4-2)
EFT (IEC 61800-5-1, IEC 61000-4-4)
Surge Test (IEC 61800-5-1, IEC 61000-4-5)
Conducted Susceptibility Test (IEC 61800-5-1, IEC 61000-4-6)
Operation/storage
Operation: -10°C ~ 50°C (temperature), 90% (humidity)
Storage: -25°C ~ 70°C (temperature), 95% (humidity)
Vibration/shock immunity
International standard: IEC 61800-5-1, IEC 60068-2-6/IEC
61800-5-1, IEC 60068-2-27
Communication Parameters for VFD-CFP2000 Connected to Ethernet
When VFD-CFP2000 is linking to Ethernet, please set up the communication parameters base
on the table below. Ethernet master will be able to read/write the frequency word and control word of
VFD-CFP2000 after communication parameters setup.
Parameter
Function Set value (Dec) Explanation
P00-20
Source of frequency
command setting
8
The frequency command is controlled by
communication card.
P00-21
Source of operation
command setting
5
The operation command is controlled by
communication card.
P09-30
Decoding method for
communication
0 Decoding method for Delta AC motor drive
P09-75
IP setting 0 Static IP(0) / Dynamic distribution IP(1)
P09-76
IP address -1 192 IP address 192.168.1.5
P09-77
IP address -2 168 IP address 192.168.1.5
P09-78
IP address -3 1 IP address 192.168.1.5
P09-79
IP address -4 5 IP address 192.168.1.5
P09-80
Netmask -1 255 Netmask 255.255.255.0
P09-81
Netmask -2 255 Netmask 255.255.255.0
P09-82
Netmask -3 255 Netmask 255.255.255.0
P09-83
Netmask -4 0 Netmask 255.255.255.0
P09-84
Default gateway -1 192 Default gateway 192.168.1.1
P09-85
Default gateway -2 168 Default gateway 192.168.1.1
P09-86
Default gateway -3 1 Default gateway 192.168.1.1
P09-87
Default gateway -4 1 Default gateway 192.168.1.1
Basic Registers
BR# R/W Content Explanation
#0 R
Model name Set up by the system; read only. The model code of
CMC-MOD01=H’0203
#1 R
Firmware
version
Displaying the current firmware version in hex, e.g. H’0100 indicates the
firmware version V1.00.
#2 R
Release date of
the version
Displaying the data in decimal form. 10,000s digit and 1,000s digit are for
“month”; 100s digit and 10s digit are for “day”.
For 1 digit: 0 = morning; 1 = afternoon.
#11 R/W Modbus Timeout Pre-defined setting: 500 (ms)
#13 R/W Keep Alive Time Pre-defined setting: 30 (s)