Chapter 2 Installation|CFP2000 Series
2-1
Chapter 2 Installation
2-1 Minimum Mounting Clearance and Installation
NOTE
; Prevent fiber particles, scraps of paper, shredded wood saw dust, metal particles, etc. from
adhering to the heat sink
; Install the AC motor drive in a metal cabinet. When installing one drive below another one,
use a metal separation between the AC motor drives to prevent mutual heating and to
prevent the risk of fire accident.
; Install the AC motor drive in Pollution Degree 2 environments only: normally only
nonconductive pollution occurs and temporary conductivity caused by condensation is
expected.
The appearances shown in the following figures are for reference only.
Airflow direction: (Blue arrow) inflow (Red arrow) outflow (Black) distance
Single drive installation
Side-by-side horizontal installation