Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-00-1
Chapter 12 Description of Parameter Settings
12-1 Description of parameter settings
00 Drive Parameters
This parameter can be set during operation.
Identity Code of the AC Motor Drive
Factory Setting: #.#
Settings Read Only
Display AC Motor Drive Rated Current
Factory Setting: #.#
Settings Read Only
Pr. 00-00 displays the identity code of the AC motor drive. Using the following table to check if
Pr.00-01 setting is the rated current of the AC motor drive. Pr.00-01 corresponds to the identity
code Pr.00-00.
The factory setting is the rated current for normal duty. Please set Pr.00-16 to 1 to display the
rated current for the heavy duty.
Frame
A B
kW 0.75 1.5 2.2 3.7 4.0 5.5 7. 5 11 15
HP 1 2 3 5 5 7.5 10 15 20
Pr.00-00 5 7 9 11 93 13 15 17 19
Rated Current for Light Duty (A) 3 4.2 5.5 8.5 10.5 13 18 24 32
Rated Current for Normal Duty (A) 1.7 3.0 4.0 6.0 9.0 10.5 12 18 24
Frame B
C
D0 D
kW 18.5 22 30
37 45 55 75 90
HP 25 30 40
50 60 75 100 125
Pr.00-00 21 23 25
27 29 31 33 35
Rated Current for Light Duty (A) 38 45 60 73 91 110 150 180
Rated Current for Normal Duty (A) 32 38 45 60 73 91 110 150
Parameter Reset
Factory Setting: 0
Settings 0: No Function
1: Parameter write protect
5: Reset KWH display to 0
6: Reset PLC (including CANopen Master Index)
7: Reset CANopen Index (Slave)
8: Reserved
9: All parameters are reset to factory settings(base frequency is 50Hz)
10: All parameters are reset to factory settings (base frequency is 60Hz)
When it is set to 1, all parameters are read only except Pr.00-02~00-08 and it can be used with
password setting for password protection. It needs to set Pr.00-02 to 0 before changing other
parameter settings.
When it is set to 9 or 10: all parameters are reset to factory settings. If password is set in
Pr.00-08, input the password set in Pr.00-07 to reset to factory settings.