Chapter 9 Specifications |CFP2000 Series
9-3
9-2 Environment for Operation, Storage and Transportation
The drive must not be exposed to dust, direct sunlight, corrosive or flammable gases, oil mist, vapor, water drops or
vibration. The atmosphere must contain only a low level of salt. (0.01 mg/cm2 or less per year)
Ambient
Conditions
Installation location IEC60364-1/IEC60664-1 Pollution degree 2, Indoor use only
Ambient
Temperature
Operation
- 15°C ~+ 50°C without derating,
+51°C ~ 60°C with derating
Storage
-25
o
C ~ +70
o
C
Transportation
-25
o
C ~ +70
o
C
Non-condensation, non-frozen
Rated Humidity
Operation
Max. 95%
Storage/
Transportation
Max. 95%
No condense allowed
Atmospheric
Pressure
Operation/
Storage
86 to 106 kPa
Transportation
70 to 106 kPa
Withstand to harsh
environments
IEC 60721-3
Operation
Class 3C3; Class 3S2; Class 3B1
Storage
Class 1C2; Class 1S2
Transportation
Class 2C2; Class 2S2
Altitude
Operation
Rated current available at 0 to 1000 m, reduced by 1% per 100 m over 1000 to
3000 m. Limited to 2000 m for the “Corner Grounded” distribution network.
Vibration
Operating
IEC 60068-2-6
Frame A: 2Hz≦f≦13.2Hz/Amplitude 1mm; 13.2Hz<f≦55Hz/Gravity 0.7G to 2.0G; 55Hz<f≦
512Hz/Gravity 2.0G
Frame B: 2Hz≦f≦13.2Hz/Amplitude 1mm; 13.2Hz<f≦55Hz/Gravity 0.7G to 1.5G; 55Hz<f≦
512Hz/Gravity 1.5G
Frame C;D0;D:A: 2Hz≦f≦13.2Hz/Amplitude 1mm; 13.2Hz<f≦55Hz/Gravity 0.7G to 1.0G; 55Hz<f≦
512Hz/Gravity 1.0G
Shock
Operating
IEC 60068-2-27
Frame A;B;C;D0: Max 30G;11 ms
Frame D: Max 15G;11 ms
In protective
shipping
package
Vibration
IEC 60068-2-64
10Hz
≦
f
≦
100Hz/ASD
:
1.0m2/s3
100Hz
≦
f
≦
200Hz/ Slope
:
-3dB/octave
Shock
Cardboard box type: Free fall drop in accordance with ISTA 1