Chapter 2 Installation|CFP2000 Series
2-2
Multiple drives side-by-side vertical installation
When installing one AC motor drive below another one (top-bottom installation), use a metal separation
between the drives to prevent mutual heating. The temperature measured at the fan’s inflow side must be
lower than the temperature measured at the operation side. If the fan’s inflow temperature is higher, use
a thicker or larger size of metal partition. Operation temperature is the temperature measured at 50mm
away from the fan’s inflow side. (As shown in the figure below)
Ta=50
2-2 Minimum mounting clearance
Frame A (mm) B (mm) C (mm) D (mm)
A~B 60 15 -
-
C~D 100 25 -
-
Frame A
VFD007FP4EA-41, VFD007FP4EA-52, VFD007FP4EA-52S,
VFD015FP4EA-41, VFD015FP4EA-52, VFD015FP4EA-52S,
VFD022FP4EA-41,VFD022FP4EA-52, VFD022FP4EA-52S,
VFD037FP4EA-41,VFD037FP4EA-52, VFD037FP4EA-52S,
VFD040FP4EA-41,VFD040FP4EA-52, VFD040FP4EA-52S,
VFD055FP4EA-41,VFD055FP4EA-52, VFD055FP4EA-52S,
VFD075FP4EA-41, VFD075FP4EA-52, VFD075FP4EA-52S
Frame B
VFD110FP4EA-41,VFD110FP4EA-52, VFD110FP4EA-52S,
VFD150FP4EA-41,VFD150FP4EA-52, VFD150FP4EA-52S,
VFD185FP4EA-41,VFD185FP4EA-52, VFD185FP4EA-52S,
VFD220FP4EA-41, VFD220FP4EA-52, VFD220FP4EA-52S
Frame C
VFD300FP4EA-41, VFD300FP4EA-52, VFD300FP4EA-52S,
VFD370FP4EA-41,VFD370FP4EA-52, VFD370FP4EA-52S
Frame D0
VFD450FP4EA-41,VFD450FP4EA-52, VFD450FP4EA-52S,
VFD550FP4EA-41,VFD550FP4EA-52, VFD550FP4EA-52S
Frame D
VFD750FP4EA-41,VFD750FP4EA-52, VFD750FP4EA-52S,
VFD900FP4EA-41,VFD900FP4EA-52, VFD900FP4EA-52S