Chapter 2 Installation|CFP2000 Series
2-3
NOTE
1. The minimum mounting clearances stated in the table above applies to AC motor drives frame A to D. A drive fails
to follow the minimum mounting clearances may cause the fan to malfunction and heat dissipation problem.
NOTE
The mounting clearance stated in the figure is for installing the drive in an
open area. To install the drive in a confined space (such as cabinet or
electric box), please follow the following three rules: (1) Keep the minimum
mounting clearances. (2) Install a ventilation equipment or an air conditioner
to keep surrounding temperature lower than operation temperature.
The following table shows the heat dissipation and the required air
volume when installing a single drive in a confined space. When
installing multiple drives, the required air volume shall be multiplied
by the number the drives.
Refer to the chart (Air flow rate for cooling) for ventilation equipment
design and selection.
Refer to the chart (Power dissipation) for air conditioner design and
selection.
Model No.
Air flow rate for cooling Power dissipation of AC motor drive
Flow Rate (cfm) Power Dissipation (watt)
External Internal Total Loss External Internal Total
VFD007FP4EA-41/ 52 / 52S - 14 14 32 20 52
VFD015FP4EA-41/ 52 / 52S - 14 14 43 21 64
VFD022FP4EA-41/ 52 / 52S 34 14 48 74 25 99
VFD037FP4EA-41/ 52 / 52S 34 14 48 92 26 118
VFD040FP4EA-41/ 52 / 52S 34 14 48 113 26 139
VFD055FP4EA-41/ 52 / 52S 34 14 48 139 27 166
VFD075FP4EA-41/ 52 / 52S 34 14 48 195 29 224
VFD110FP4EA-41/ 52 / 52S 88 14 102 240 34 274
VFD150FP4EA-41/ 52 / 52S 88 14 102 309 38 347
VFD185FP4EA-41/ 52 / 52S 88 14 102 353 39 392
VFD220FP4EA-41/ 52 / 52S 88 14 102 449 47 496
VFD300FP4EA-41/ 52 / 52S 200 29 229 618 84 702
VFD370FP4EA-41/ 52 / 52S 200 29 229 726 87 813
VFD450FP4EA-41/ 52 / 52S 285 29 314 864 82 946
VFD550FP4EA-41/ 52 / 52S 285 29 314 1068 84 1152
VFD750FP4EA-41/ 52 / 52S 330 29 359 1407 111 1518
VFD900FP4EA-41/ 52 / 52S 330 29 359 1623 114 1737
The required airflow shown
in chart is for installing single
drive in a confined space.
The heat dissipation shown in the
chart is for installing single drive in
a confined space.