Chapter 2 Installation|CFP2000 Series 
 
 
2-3
NOTE
 
1.  The minimum mounting clearances stated in the table above applies to AC motor drives frame A to D. A drive fails 
to follow the minimum mounting clearances may cause the fan to malfunction and heat dissipation problem.     
 
 
NOTE
 
※  The mounting clearance stated in the figure is for installing the drive in an 
open area. To install the drive in a confined space (such as cabinet or 
electric box), please follow the following three rules: (1) Keep the minimum 
mounting clearances. (2) Install a ventilation equipment or an air conditioner 
to keep surrounding temperature lower than operation temperature.   
※  The following table shows the heat dissipation and the required air 
volume when installing a single drive in a confined space. When 
installing multiple drives, the required air volume shall be multiplied 
by the number the drives.
 
※  Refer to the chart (Air flow rate for cooling) for ventilation equipment 
design and selection.   
※  Refer to the chart (Power dissipation) for air conditioner design and 
selection.  
 
 
Model No. 
Air flow rate for cooling  Power dissipation of AC motor drive
Flow Rate (cfm)  Power Dissipation (watt) 
External  Internal  Total Loss External  Internal  Total 
VFD007FP4EA-41/ 52 / 52S  -  14  14  32  20  52 
VFD015FP4EA-41/ 52 / 52S  -  14  14  43  21  64 
VFD022FP4EA-41/ 52 / 52S  34  14  48  74  25  99 
VFD037FP4EA-41/ 52 / 52S  34  14  48  92  26  118 
VFD040FP4EA-41/ 52 / 52S  34  14  48  113  26  139 
VFD055FP4EA-41/ 52 / 52S  34  14  48  139  27  166 
VFD075FP4EA-41/ 52 / 52S  34  14  48  195  29  224 
VFD110FP4EA-41/ 52 / 52S  88  14  102  240  34  274 
VFD150FP4EA-41/ 52 / 52S  88  14  102  309  38  347 
VFD185FP4EA-41/ 52 / 52S  88  14  102  353  39  392 
VFD220FP4EA-41/ 52 / 52S  88  14  102  449  47  496 
VFD300FP4EA-41/ 52 / 52S  200  29  229  618  84  702 
VFD370FP4EA-41/ 52 / 52S  200  29  229  726  87  813 
VFD450FP4EA-41/ 52 / 52S  285  29  314  864  82  946 
VFD550FP4EA-41/ 52 / 52S  285  29  314  1068  84  1152 
VFD750FP4EA-41/ 52 / 52S  330  29  359  1407  111  1518 
VFD900FP4EA-41/ 52 / 52S  330  29  359  1623  114  1737 
 
※  The required airflow shown 
in chart is for installing single 
drive in a confined space.   
※  The heat dissipation shown in the 
chart is for installing single drive in 
a confined space.