Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-00-2
When it is set to 5, KWH display value can be reset to 0 even when the drive is operating. Pr.
05-26, 05-27, 05-28, 05-29, 05-30 reset to 0.
When it is set to 6: clear internal PLC program (includes the related settings of PLC internal
CANopen master)
When it is set to 7: reset the related settings of CANopen slave.
When it is set to 67910, please re-power the motor drive after setting.
Start-up Display Selection
Factory setting: 0
Settings 0: Display the frequency command (F)
1: Display the actual output frequency (H)
2: Display User define (U)
3: Output current ( A)
This parameter determines the start-up display page after power is applied to the drive. User
defined choice display according to the setting in Pr.00-04.
Content of Multi-function Display
Factory setting: 3
Settings
0: Display output current (A) (Unit: Amps)
1: Display counter value (c) (Unit: CNT)
2: Display actual output frequency (H) (Unit: Hz)
3: Display DC-BUS voltage (v) (Unit: Vdc)
4: Display output voltage (E) (Unit: Vac)
5: Display output power angle (n) (Unit: deg)
6: Display output power in kW (P) (Unit: Kw)
7: Display actual motor speed rpm (r = 00: positive speed; -00 negative
speed) (Unit: rpm)
8: Reserved
9: Reserved
10: Display PID feedback (b) (Unit: %)
11: Display AVI in % (1.), 0~10V/4-20mA/0-20mA corresponds to 0~100%
(Refer to Note 2) (Unit: %)
12: Display ACI in % (2.), 4~20mA/0~10V/0-20mA corresponds to
0~100%Refer to Note 2(Unit: %)
13: Display AUI in % (3.), -10V~10V corresponds to -100~100% (Refer to
Note 2) (Unit: %)
14: Display the temperature of IGBT (i.) (Unit: )
15: Display the temperature of capacitance (c.) (Unit: )
16: The status of digital input (ON/OFF) refer to Pr.02-12 (i) (Refer to
Note3)
17: Display digital output status ON/OFF (Pr.02-18) (o) (refer to NOTE 4)
18: Display the multi-step speed that is executing (S)