Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-00-3
19: The corresponding CPU pin status of digital input (d) (refer to NOTE 3)
20: The corresponding CPU pin status of digital output (O.) (refer to NOTE
4)
21~24: Reserved
25: Overload counting (0.00~100.00%) (h.) (Refer to Note 6) (Unit: %)
26: GFF Ground Fault (G.) (Unit: %)
27: DC Bus voltage ripple (r.) (Unit: %)
28: Display PLC register D1043 data (C) display in hexadecimal
29: Reserved
30 : Display output of user defined (U)
31 : H page x 00-05 Display user Gain(K)
32~33: Reserved
34: Operation speed of fan (F.) (Unit: %)
35: Reserved
36: Present operating carrier frequency of drive (Hz) (J.)
37: Reserved
38: Display drive status (6.) (Refer to Note 7)
39~40: Reserved
41: KWH display (J) (Unit: KWH)
42: PID reference (h) (Unit: %)
43: PID offset (o.) (Unit: %)
44: PID output frequency (b.) (Unit: Hz)
45: Hardware ID (0)
NOTE
1. When Pr.10-01 is set to 1000 and Pr.10-02 is set to 1/2, the display range for PG feedback will be
from 0 to 4000.
When Pr.10-01 is set to 1000 and Pr.10-02 is set to 3/4/5, the display range for PG feedback will be
from 0 to 1000.
Home position: If it has Z phase, Z phase will be regarded as home position. Otherwise, home
position will be the encoder start up position.
2. It can display negative values when setting analog input bias (Pr.03-03~03-10).
Example: assume that AVI input voltage is 0V, Pr.03-03 is 10.0% and Pr.03-07 is 4 (Serve bias as the
center).
3. Example: If REV, MI1 and MI6 are ON, the following table shows the status of the terminals.
0: OFF, 1: ON
Terminal MI15 MI14 MI13 MI12 MI11 MI10 MI8 MI7 MI6 MI5 MI4 MI3 MI2 MI1 REV FWD
Status 0 0 0 0 0 0 0010000
1 1 0
MI10~MI15 are the terminals for extension cards (Pr.02-26~02-31).
If REV, MI1 and MI6 are ON, the value is 0000 0000 1000 0110 in binary and 0086h in HEX. When
Pr.00-04 is set to “16” or “19”, it will display “0086h” with LED U is ON on the keypad KPC-CE01. The
setting 16 is the status of digital input by Pr.02-12 setting and the setting 19 is the corresponding CPU
pin status of digital input, the FWD/REV action and the three-wire MI are not controlled by Pr.02-12.
User can set to 16 to monitor digital input status and then set to 19 to check if the wire is normal.
4. Assume that RY1: Pr.02-13 is set to 9 (Drive ready). After applying the power to the AC motor drive, if
there is no other abnormal status, the contact will be ON. The display status will be shown as
follows.