Chapter 12 Description of Parameter Settings|CFP2000 Series 
 
12.1-00-4 
N.O. switch status: 
Terminal MO20~MO17  MO16~MO13 MO12~MO10 Reserved Reserved  RY3  RY2 RY1
Status 0 0 0 0 0 0 0 0 0 0 0 0 0  0  0 0 1 
At the meanwhile, if Pr.00-04 is set to 17 or 20, it will display in hexadecimal “0001h” with LED U is 
ON on the keypad. The setting 17 is the status of digital output by Pr.02-18 setting and the setting 20 
is the corresponding CPU pin status of digital output. User can set 17 to monitor the digital output 
status and then set to 20 to check if the wire is normal. 
5.  Setting 8: 100% means the motor rated torque. Motor rated torque = (motor rated power 
x60/2π)/motor rated speed 
6.  If Pr.00-04 = 25, when display value reaches 100.00%, the drive will show “oL” as an overload 
warning. 
7.  If Pr.00-04 = 38,   
Bit 0: The drive is running forward. 
Bit 1: The drive is running backward. 
Bit 2: The drive is ready. 
Bit 3: Errors occurred on the drive. 
Bit 4: The drive is running. 
Bit 5: Warnings on the drive. 
 
 
Coefficient Gain in Actual Output Frequency 
 
 
  Factory Setting: 1.00
  Settings  0.00~160.00 
 This parameter is to set coefficient gain in actual output frequency. Set Pr.00-04= 31 to display 
the calculation result on the screen (calculation = output frequency * Pr.00-05).   
 
 
Software Version 
 
 
  Factory Setting: #.# 
  Settings  Read only 
 
 
Parameter Protection Password Input 
 
 
  Factory Setting: 0 
  Settings  1~9998, 10000~65535 
  Display  0~4 (the times of password attempts) 
 This parameter allows user to enter their password (which is set in Pr.00-08) to unlock the 
parameter protection and to make changes to the parameter.   
 Pr.00-07 and Pr.00-08 are used to prevent the personal miss-operation. 
 When the user have forgotten the password, clear the setting by input 9999 and press ENTER 
key, then input 9999 again and press Enter within 10 seconds. After decoding, all the settings will 
return to factory setting. 
 
 
Parameter Protection Password Setting   
 
 
  Factory Setting: 0 
  Settings  1~9998, 10000~65535 
    0: No password protection / password is entered correctly (Pr00-07) 
    1: Password has been set 
   To set a password to protect your parameter settings. In the first time, password can be set