Chapter 12 Description of Parameter Settings|CFP2000 Series 
 
12.1-00-5 
directly. After setting, the value of 00-08 will become 1, which means password protection is 
activated. When the password is set, if any parameter setting needs to be changed, be sure to 
enter correct password in 00-07, and then the password will be inactivated temporarily with 
00-08 changing to 0. At this time, parameters setting can be changed. After setting, re-power 
the motor drive, and password will be activated again. 
 To cancel the password protection, after entering correct password in 00-07, 00-08 also needs to 
be set as 0 again to inactive password protection permanently. If not, password protection will 
be active after motor drive re-power. 
 The keypad copy function will work normally only when the password protection is inactivated 
temporarily or permanently, and password set in 00-08 will not be copied to keypad. So when 
copying parameters from keypad to motor drive, the password need to be set manually again in 
the motor drive to active password protection.
 
Password Decode Flow Chart 
Password Setting
Password Forgotten
Enter 9999 and press ENTER,
then enter 9999 again within 10 
seconds
 
 and press ENTER.
Then all  para meters will re set 
to factory settings.
Displays 01 after 
correct password is 
entered to Pr.00-08.
3 chances of password input:
Incorrect password 1:
 displays "02"
Incorrect password 3: "Pcode"(blinking) 
 displays "01" 
Incorrect password 2: 
Keypad will be locked after  3 wrong attempted
passwords.  To re-activate the keypad, please
reboot the drive  and  input the correct 
password.
Password Incorrect
00-07
00-08
00-07
 
00-08
00-07
Decode Flow Chart
Password Set
Password Input
 Pr.00-08=0
Yes
No
Shut down th drive
and re-apply  power
Re-apply power.
(The password is still valid)
 
 
 
Reserved 
 
 
Reserved 
 
 
 
Control of Speed Mode 
 
 
  Factory Setting: 0 
   Settings  0: VF (IM V/f control) 
     2: SVC(IM/PM sensorless vector control) 
 This parameter determines the control method of the AC motor drive: 
0: (IM V/f control): user can design proportion of V/f as required and can control multiple