Chapter 12 Description of Parameter Settings|CFP2000 Series
12.1-00-5
directly. After setting, the value of 00-08 will become 1, which means password protection is
activated. When the password is set, if any parameter setting needs to be changed, be sure to
enter correct password in 00-07, and then the password will be inactivated temporarily with
00-08 changing to 0. At this time, parameters setting can be changed. After setting, re-power
the motor drive, and password will be activated again.
To cancel the password protection, after entering correct password in 00-07, 00-08 also needs to
be set as 0 again to inactive password protection permanently. If not, password protection will
be active after motor drive re-power.
The keypad copy function will work normally only when the password protection is inactivated
temporarily or permanently, and password set in 00-08 will not be copied to keypad. So when
copying parameters from keypad to motor drive, the password need to be set manually again in
the motor drive to active password protection.
Password Decode Flow Chart
Password Setting
Password Forgotten
Enter 9999 and press ENTER,
then enter 9999 again within 10
seconds
and press ENTER.
Then all para meters will re set
to factory settings.
Displays 01 after
correct password is
entered to Pr.00-08.
3 chances of password input:
Incorrect password 1:
displays "02"
Incorrect password 3: "Pcode"(blinking)
displays "01"
Incorrect password 2:
Keypad will be locked after 3 wrong attempted
passwords. To re-activate the keypad, please
reboot the drive and input the correct
password.
Password Incorrect
00-07
00-08
00-07
00-08
00-07
Decode Flow Chart
Password Set
Password Input
Pr.00-08=0
Yes
No
Shut down th drive
and re-apply power
Re-apply power.
(The password is still valid)
Reserved
Reserved
Control of Speed Mode
Factory Setting: 0
Settings 0: VF (IM V/f control)
2: SVC(IM/PM sensorless vector control)
This parameter determines the control method of the AC motor drive:
0: (IM V/f control): user can design proportion of V/f as required and can control multiple